Revision as of 20:03, 23 September 2017
Overview
This page only applies for the following models:
RPICT7V1 Version 2
RPICT4V3 Version 2
RPICT8
All RPICT boards can be configured to output the data in the Emoncms format.
Preliminaries
The Raspberrypi must use the software image provided by Emoncms. Refer to Emoncms website to find out which SD card image to use.
Steps
-1-
Before we start any work we will have to close down emonhub so we can have free access to the serial port.
$ /etc/init.d/emonhub stop
-2-
Grab the configuration that you need for your board using one of the command below. Note the example below if for sketch version 2.5 (replace B2 with B1 in the link if using sketch version 2.4)
RPICT7V1
$ wget lechacal.com/RPICT/config/B2/rpict7v1.conf $ ./lcl-rpict-config.py -w rpict7v1.conf
RPICT8
$ wget lechacal.com/RPICT/config/B2/rpict8.conf $ ./lcl-rpict-config.py -w rpict8.conf
RPICT4V3
$ wget lechacal.com/RPICT/config/B2/rpict4v3.conf $ ./lcl-rpict-config.py -w rpict4v3.conf
-3-
Edit the file using nano. For example:
$ nano rpict7v1.conf
modify the line that says
format = 0
into
format = 1
Save and exit the file
-4-
Get the latest lcl utility program.
$ wget lechacal.com/RPICT/lcl-rpict-config.py.zip $ unzip lcl-rpict-config.py.zip
-5-
Write the configuration to the board:
$ ./lcl-rpict-config.py -w rpict7v1.conf
-6-
Once the configuration write successful start the emonhub again
$ /etc/init.d/emonhub start
Output as float [OPTIONAL]
By default the Emoncms format only has integers. One might find better to use floats instead.
To do this use the format parameter as follow:
format = 2
Once complete you will need to inform the emonhub that it should read floats and not intergers. This indicated with a 'f' in the datatype parameters.
An example below:
[[11]] nodename = my_RPICT7V1 firmware = v2.5 hardware = RPICT7V1 [[[rx]]] names = Realpower1, Realpower2, Realpower3, Realpower4, Realpower5, Realpower6, Realpower7, Irms1, Irms2, Irms3, Irms4,Irms5,Irms6,Irms7,Vrms datacode = f,f,f,f,f,f,f,f,f,f,f,f,f,f,f scales = 1,1,1,1,1,1,1,1,1,1,1,1,1,1,1 units =W,W,W,W,W,W,W,mA,mA,mA,mA,mA,mA,mA,V