Gen5 Passive Component Setup: Difference between revisions
Jump to navigation
Jump to search
Line 24: | Line 24: | ||
|- | |- | ||
| 60 | | 60 | ||
| | | 47 | ||
| | | 42.55 | ||
|- | |- | ||
| 50 | | 50 | ||
| | | 56 | ||
| | | 35.71 | ||
|- | |- | ||
| 30 | | 30 | ||
| | | 91 | ||
| | | 21.978 | ||
|- | |- | ||
| 25 | | 25 | ||
| | | 110 | ||
| | | 18.182 | ||
|- | |- | ||
| 20 | | 20 | ||
| | | 140 | ||
| | | 14.286 | ||
|- | |- | ||
| '''SCT-006-000''' | | '''SCT-006-000''' |
Revision as of 18:51, 17 September 2020
Vref = 4.096V
CT Current Transformers
Sensor | Range (Rms Amps) |
Burden Resistor RD1 (Ω) |
Calibration Coefficient (theoretical) |
---|---|---|---|
SCT-019-000 | |||
SCT-013-000 | 100 | 27 | 74.074 |
60 | 47 | 42.55 | |
50 | 56 | 35.71 | |
30 | 91 | 21.978 | |
25 | 110 | 18.182 | |
20 | 140 | 14.286 | |
SCT-006-000 | 20 | 10 | 0 |
SCT-024 400:5 | 400 |
AC Voltage
Sensor | Range (Rms Amps) |
Burden Resistor RD1 (Ω) |
Dividing Resistor RD2(Ω) |
Gain Resistor RF (Ω) |
Gain Resistor RG (Ω) |
Calibration Coefficient (theoretical) |
---|---|---|---|---|---|---|
Any Ideal Power | 33 kΩ | 470 kΩ | No | 322.5 (experimental) | ||
ZMPT101B 160kΩ in 100Ω out Sensitivity 0.625mv/V |
430V | No | 0 Ω | 22kΩ | 356.7 |
Vref = 3.3V
Sensor | Range (Rms Volts) |
Burden Resistor Rb (Ω) |
Dividing Resistor (Ω) |
Gain Resistor Rg (Ω) |
Calibration Coefficient (theoretical) |
---|---|---|---|---|---|
Any Ideal Power | |||||
ZMPT101B 160kΩ in 100Ω out sensitity 0.625mV/V |
280V | No | 0 Ω | 22K | 284.37 (exp) |