Burden Resistor calculation: Difference between revisions

From lechacal
Jump to navigation Jump to search
Line 11: Line 11:
:SCT-019 is 6000.<br>
:SCT-019 is 6000.<br>
:SCT-006 is  800.<br>
:SCT-006 is  800.<br>
'''Irms''': Max current to be read in rms<br>
'''Irms''': Max current to be read in Ampere (rms)<br>


==Current Coefficient Formulae==
==Current Coefficient Formulae==

Revision as of 12:45, 3 March 2019


Burden Resistor Formulae

R = (Vcc * Nturns) / (2√2 * Irms)

R: Burden resistor value in Ohm
Vcc: ADC max voltage range (usually 3.3V)
Nturns: Number of CT sensor turns (see specs).

SCT-013 is 2000 turns.
SCT-019 is 6000.
SCT-006 is 800.

Irms: Max current to be read in Ampere (rms)

Current Coefficient Formulae

This will compute ICAL.

ICAL = Nturns / R

ICAL: Current Coefficient
Nturns: Number of CT sensor turns
R: Burden resistor value in Ohm