The relation between the peak voltage from the CT at full scale and the Gain is given by
The relation between the peak voltage from the CT at full scale and the Gain is given by


  G * Vct = Vadc/2
  Vct * G = Vadc/2


'''Vct'''  - Secondary peak voltage of the CT sensor.
'''Vct'''  - Secondary peak voltage of the CT sensor.

Revision as of 21:18, 7 April 2019


UNDER CONSTRUCTION...


Gain formulae

Given a desired Gain the Gain resistor Rg can be calculated as follow.

Rg = 100000/(G -1)

G is the Amplification Gain.
Rg is the resistor value in ohm.

or deducing the gain from the resistor will be using

G = 100000/Rg + 1

ADC Full Scale

The RPICT7V1 Version 4 uses 4.096V voltage reference for the ADC. Signals are centred on 2.048V. Therefore the waveform can have a max amplitude of 2.048V. We will call this Vadc/2.

Vadc = 4.096V

The relation between the peak voltage from the CT at full scale and the Gain is given by

Vct * G = Vadc/2

Vct - Secondary peak voltage of the CT sensor.

Vct = Irms*√2/Nt * Rb

Irms - Max rms current required at full scale.
Nt - Turn Ratio of the CT sensor. Or number of turns.
Rb - Burden Resistor.

G = Vadc*Nt/(Irms*2√2*Rb)