RPICT3V1 by default outputs all channels. Which are

RealPower ApparentPower Irms Vrms PowerFactor

for all 3 Current Voltage pairs computed (ct1 ct2 ct3).

To prevent some of the channels to appear we can disable then by setting the debug variable with a particular number.

debug is coded on 8 bits where each bit correspond to the following (LSB first).

bit 1 - debug 0 = OFF 1 = ON
bit 2 - Apparent Power 1 = OFF 0 = ON
bit 3 - Irms 1 = OFF 0 = ON
bit 4 - Vrms 1 = OFF 0 = ON
bit 5 - PowerFactor 1 = OFF 0 = ON
bit 6 - ct3 1 = OFF 0 = ON
bit 7 - ct2 = OFF 0 = ON
bit 8 - ct1 1 = OFF 0 = ON

Note that RealPower is always ON and can not be disabled.

  • By default alls channels are ON and debug is OFF.

This is 00000000 in binary and 0 in decimal.

debug = 0
  • To enable debug set bit 1 to 1.

This is 00000001 in binary and 1 in decimal

debug = 1
  • To disable apparent power and enable debug then set bits 1 and 2 to 1

This is 00000011 in binary and 3 in decimal

debug = 3
  • To disable ct2 and ct3 and set debug OFF

This is 01100000 in binary and 96 in decimal

debug = 96

To convert from binary to decimal and back use this webtool here.