Vref

4.096V=

CT Current Transformers

Sensor

Range
(Rms Amps)

Burden Resistor
RD1 (Ω)

Calibration Coefficient
(theoretical)

SCT-019-000 (200A/33mA)

200

43

139.535

SCT-013-000 (100A/50mA)

100

27

74.074

60

47

42.553

50

56

35.714

40

71.5

27.972

30

91

21.978

25

110

18.182

20

140

14.286

SCT-006 (20A/25mA)

20

56

14.286

10

110

7.272

5

140

3.571

SCT-024 400A:5A

400

SCT-024 400A:100mA

400

14.3

279.72

SCT-031 600:100mA

600

14.3

419.58

AC Voltage

All voltage reported as RMS value in the table below.

Sensor

Range
@ sensor input

Range
@ board input

RD1 (Ω)

RD2(Ω)

Gain Resistor
RF (Ω)

Gain Resistor
RG (Ω)

Calibration Coefficient
(theoretical)

Any ac/ac adaptor
up to 18V output

(EU) 77DE-06-09: 360V
(UK) 77DB-06-09: 372V
(US) 77DA-10-09: 180V

18V

53.6kΩ

4.7kΩ

0

(EU) 77DE-06-09: 248.1
(UK) 77DB-06-09: 256.6
(US) 77DA-10-09: 124.0

ZMPT_1X_225*

408V

0.25V

22kΩ

4.7kΩ

281.65

RPICT4W3T1 L-L

435V

0.15V

42.2kΩ

4.7kΩ

300.64

ZMPT_1X_280

290V

0.15V

42.2kΩ

4.7kΩ

200.43

ZMPT_1X_140

145V

0.15V

42.2kΩ

4.7kΩ

100.21

  • ZMPT_1X_225 is no longer used. Listed here for reference.

See Also

Burden Resistor calculation